FORISTEK
Vol 1, No 1 (2011)

WATAK HARMONIK PADA BEBAN NON LINIER INVERTER

Sunanda, Wahri ( Universitas Bangka Belitung )
Rahman, Yuli Asmi ( Universitas Tadulako )



Article Info

Publish Date
05 Jun 2012

Abstract

Harmonic is one of sinusoidal components, one wave period from which having multiple frequency of its fundamental frequency one, leading to electrical power quality problems. Harmonic distortion in term of voltage and current ones, generally is due to non linier impedance. Inverter is one of example of it. There are some items that will be measured. There are value of harmonic at  source and value of voltage and current harmonic when inverter does not have any load. IEEE Standard of 519-1992 as a reference in determining maximum limitation voltage and current harmonics. The result of the tests were showed that voltage harmonic distortion at inverter did not exceed the IEEE 519-1992 maximum limitation of 5%. While current harmonic distortion had exceed the maximum limitation of the IEEE 519-1992. The highest results were exceeding 56,55 % when inverter does not have any load. Keywords : Voltage, Current, Harmonic Distortion, Inverter.

Copyrights © 2011






Journal Info

Abbrev

FORISTEK

Publisher

Subject

Other

Description

Jurnal ilmiah FORISTEK merupakan wadah bagi para profesional untuk mempublikasikan karya ilmiah baik itu bersifat hasil penelitian maupun studi literatur dalam bidang teknik elektro dan teknologi informasi.Jurnal ini terbit dua kali setahun yaitu pada bulan maret dan ...